Resolve problems with Node-RED and OPC-UA connection

From time to time, the OPC UA module in Node-RED doesn't always want to connect to our OPC UA server after installation.

The reason is that the installation doesn't always create the necessary self-signed certificates which are needed.

This blog will show you how to create those certificates on the controller and how to get your OPC UA connection up and running in Node-RED.

Creation of the certificates

Sign in into the controller with your admin credentials. Once signed in, execute the following command:

openssl req -newkey rsa:1024 -nodes -keyout private_key.pem -x509 -out client_selfsigned_cert_1024.pem

This command will prompt you for some extra information like your name, company, location, ... which will be used to create the certificate.

Linking the certificates

After the certificates are created, you have two options in order to use them.

Placing them in the default directory

You can use them by placing them directly in the standard location, this can be done by searching your node_modules folder.

From thereon you can place the certificate in:

../node-opcua-client/certificates

and the key in:

../node-opcua-client/certificates/PKI/own/private

Note that this last folder will already have a key file with the same name. I advice to rename the original before moving your file into this location.

Linking them from the Node-RED webpage

When you create the OPCUA-IIoT-Connector node, you can check the checkbox "use individual certificate files" and link to both files which you created in the beginning.

Node RED certificates

After a restart of Node-RED your OPC UA communication should be up and running!

Comments  

# tono 2020-02-03 20:48
Nice to know. I am struggling with exactly this issue at the moment. But I`m not very experienced with this... What is the folder location on PLC Next controller for the Certificate and Private key after generating them?