If done the update to 1.02 this week and after the update an existing project does not start anymore. I have some C++ library if written and a simple application with some IO's. With the original firmware the project was working without any Porblems. But now if I try to download the application to the AXC 2152 is not connectable from PCWorxEngineer. With WinSCP I could connect.

When I remove the Project from the PLC, The AXC 2152 is starting again and I could work normally. A simple project adressing some DOs only with IEC 61131 code also works.

Accepted Answer
Vincent PLCnext Team Accepted Answer Pending Moderation
0
Votes
Undo

Did you upgrade from version 1.0.0? if so, you probably haven't updated the C++ SDK.

This is mandatory to get the latest C++-sdk, and recompile your library.

Phoenix Contact Netherlands - Technical Consultant

pynl02 Accepted Answer Pending Moderation
0
Votes
Undo

Works for thanks. Do I always need to update the SDK? Were kann I get information about the fact that a new SDK is needed for a Firmware version?

Dzmitry Ivaniuk Accepted Answer Pending Moderation
0
Votes
Undo

Hello,

As variant you can check download area for corresponding SDK versions.