This site uses cookies for functional purposes. To continue please read and agree to our Data Privacy.

By closing this message, you consent to our use of cookies on this device.

Share questions in our PLCnext forum

  1. jimmypesto
  2. PC Worx Engineer
  3. Wednesday, 28 November 2018
  4.  Subscribe via email

Hallo,

I would like to send TCP commandos via FB. I got the TCP_SOCKET connected but somehow I am not able to set the DATA input of the TCP_SEND FB.
In the help section it says DATA has datatype "ANY". I have tried to set a string and an buffer as DATA input (also tried to connect it to the DATA output).

But I always get the error message: "FBDP0001 Objekt ist nicht verbunden" -> Object is not connected

Clicking on the error highlights the DATA input port of the TCP_SEND FB.

Connecting one String as input and an other String as output to the DATA parameter the following error is thrown:
"FBDP0012 VAR_IN_OUT-Parameter ist nicht korrekt verbunden" -> parameter is not connected correctly

 

How do i connect the String i want to send via TCP to the DATA parameter of TCP_SEND?

 

Edit:
Ok. With a second FB-link to my String variable I was able to bind the String to the in- and outport of the TCP_SEND FB.
Now I´m able to compile.

 

Greetings,

Jimmy Pesto

Accepted Answer
Eduard PLCnext Team Accepted Answer Pending Moderation
0
Votes
Undo

Hello Jimmy,

I assume the cause of error is the not connected IN/OUT Variable from the "TCP_Send" / "TCP_Receive" FB or the wrong datatypes. Please find below the screenshot of working application and the used datatypes. I have downloaded the PCWorxEngineer program on two AXCF2152 controller (for transmit and receive of TCP IP telegrams). If you have additionally questions, please don't hesitate to ask !

First AXC2152 Controller: The application receives the TCP-Telegram

 

Second AXC2152 Controller: The application sends the TCP-Telegram

 

Used datatypes:

Best Regards

Eduard


Phoenix Contact Electronics Headquarter - Support Center

  1. more than a month ago
  2. PC Worx Engineer
  3. # Permalink
Frank PLCnext Team Accepted Answer Pending Moderation
0
Votes
Undo

Hi Jimmy,

sorry for the delay.

In the last week we were more or less all busy on an the PLC/Drives in Nuremberg.

We will come back to you asap.

cu

Frank


Phoenix Contact Electronics Headquarter - Support Center

  1. more than a month ago
  2. PC Worx Engineer
  3. # 1
jimmypesto Accepted Answer Pending Moderation
0
Votes
Undo

Thanks for your help. Using datatype "PND_IO_512" and connecting two instances of the same variable as "in" and "out" port solved my problem!

May I ask you an other quick question?

I need to poll some web inputs via these TCP-Requests. Therefore I want to send the request as often as possible.
How can I trigger sending the request everytime the last request was finished?
I tried to use some Flipflops and the TCP-SEND "busy" and "done" outputs but this somehow gets stuck sometimes.

Thanks a lot for your advice!

Greetings,

Jimmy

  1. more than a month ago
  2. PC Worx Engineer
  3. # 2
Martin PLCnext Team Accepted Answer Pending Moderation
0
Votes
Undo

Hi Jimmy,

How can I trigger sending the request everytime the last request was finished?

Using Eduard's example (above) as a reference, you should be able to use something like this before the call to the TCP_SEND function block ...

xRequest := TCP_SOCKET_1.ACTIVE AND NOT TCP_SEND_1.BUSY;

This will toggle the REQ input every time the BUSY output goes low.

It's always worth putting in a timeout in situations like this, just in case things get stuck for any unforseen reason. For example, you could use a TON timer to reset the REQ input in cases where the BUSY output never appears, or is missed for some reason:

TIMEOUT(IN:=xRequest, PT:=T#10S);
xRequest := TCP_SOCKET_1.ACTIVE AND NOT TCP_SEND_1.BUSY AND NOT TIMEOUT.Q;

I haven't tested the above code, but something like this should help.

- Martin.

Phoenix Contact Electronics Headquarters - Support Center

  1. more than a month ago
  2. PC Worx Engineer
  3. # 3
  • Page :
  • 1


There are no replies made for this post yet.
However, you are not allowed to reply to this post.

We have 81 guests and 2 members online