also I download project to device already.

But can't debug like other .

varottaritk Accepted Answer Pending Moderation
0
Votes
Undo

Capture 2019

  1. more than a month ago
  2. PLCnext Engineer
  3. # 1
Martin PLCnext Team Accepted Answer Pending Moderation
0
Votes
Undo

Hello,

I can reproduce this, but only if the online and offline projects do not match. Are you 100% sure that you were able to download the project to the PLC successfully?

What version of PLCnext Engineer you are using, and what PLC firmware version?

I see that the FAIL LED is lit. I am guessing that the RUN LED is flashing, so this indicates that the PLC program has stopped. If you are trying to diagnose the reason for this, then you can check the file /opt/plcnext/logs/Output.log, where you may see an entry like this:

12.07.19 01:22:08.929 Arp.Plc.Esm.Internal.TaskScheduler ERROR - Watchdog of task 'Cyclic100' triggered. (watchdog time 100000us / time after task start 100454us)

 

(I have also moved this post to the PLCnext Engineer category).

Phoenix Contact Electronics Headquarters - PLCnext Runtime Product Management and Support