PLCnext on LinkedInPLCnext on Instagram  PLCnext on YouTube Github PLCnext CommunityStore PLCnext Community

  1. chenshijin
  2. PLCnext Engineer
  3. Monday, 15 July 2019

Hello:

The context menu "Replace" of PLCnext Engineer is always grey for controller or module in version 2019.3 or 2019.6. 

I update the PLCnext Engineer and the firmware of the axc f 2152 from 2019.3 to 2019.6.

Then I use PLCnext Engineer(2019.6) opened a program designed by PLCnext Engineer(2019.3) and updated the program.

But I can't replace the controller from  axc f 2152(FW 2019.3) to axc f 2152(FW 2019.6) in the program.

who can tell me how to replace controller from  axc f 2152(FW 2019.3) to axc f 2152(FW 2019.6) in the PLCnext Engineer.

Thanks a lot.

Accepted Answer
Martin PLCnext Team Accepted Answer Pending Moderation
0
Votes
Undo

Hello,

Right-click on the new PLC type (in the Network -> Axiocontrol -> Devices -> Controller section of the Components pane) and select "Copy".

Right-click on the current PLC instance and select "Replace".

(or drag and drop)

Martin.

Phoenix Contact Electronics Headquarters - PLCnext Runtime Product Management and Support

  1. more than a month ago
  2. PLCnext Engineer
  3. # Permalink
chenshijin Accepted Answer Pending Moderation
0
Votes
Undo

Hello Martin: 

Thank you very much!

  1. more than a month ago
  2. PLCnext Engineer
  3. # 1
Frank PLCnext Team Accepted Answer Pending Moderation
0
Votes
Undo

Hi Chenshijn,

there is also a FAQ for this, please check the following link.

How to replace the controller template

Take care!


Phoenix Contact Electronics Headquarter - PLCnext Runtime Product Management and Support

  1. more than a month ago
  2. PLCnext Engineer
  3. # 2
  • Page :
  • 1


There are no replies made for this post yet.
However, you are not allowed to reply to this post.