Security Profile: Configuring OPC UA Server The OPC UA Server is activated by default. Note: If you do not use the software update via Device and Update Management, you must deactivate the OPC UA server. You have to make some settings in the OPC UA Client. Read More
Security Profile: Activating OPC UA® Client To activate OPC UA® Client, proceed as follows: Log in to the WBM. Return to topicHow do I get to the WBM again? Click here for more information… Establishing a connection to the Web-based Management (WBM): Open a web browser… Read More
Security Profile: Checking project integrity Integrity check Libraries and projects in PLCnext Engineer are hashed. The hashes assigned with PLCnext Engineer are checked by PLCnext Control. This way you can verify that data is not modified, tampered with, or corrupted. When creating the project in PLCnext Engineer, a manifest file with hashes is generated. Before… Read More
Security Profile: Activating HMI Activating PLCnext Engineer HMI For information on how to create a PLCnext Engineer HMI application, refer to the topic Creating a PLCnext Engineer HMI application in the PLCnext Technology ‑ Info Center. For information on user roles and permissions, refer to the User Authentication WBM topic in the main PLCnext Technology ‑ Info Center. Before you can use an… Read More
Security Profile: Configuring PLCnext Engineer For information on how to use PLCnext Engineer or how to create a project, refer to the Getting started with PLCnext Engineer topic in the main PLCnext Technology ‑ Info Center. Open PLCnext Engineer. Open the project that you want to transfer to the PLCnext Control. Note: You may need to assign the correct IP… Read More
Security Profile: Activating PROFINET A large port range is required for the use of PROFINET as the system automatically selects the required ports depending on the network configuration. To restrict access to the PROFINET interfaces, the IP addresses of the PROFINET devices must be configured so that only… Read More
Security Profile: Configuring Modbus TCP Client Activating the Modbus TCP Client in the system services The Modbus TCP Client is deactivated by default. To activate Modbus TCP Client, proceed as follows: Log in to the WBM. Return to topicHow do I get to the WBM again? Click here for… Read More
Security Profile: Creating users The Admin can only configure the system. All other activities must be performed by other users with other roles. You need at least a Security Engineer to access the security notifications, an Engineer to program in PLCnext Engineer and an Operator to operate an HMI. Read More
Security Profile: Account management Operating a PLCnext Control in a security context includes the following steps regarding account management: Creating users Password complexity rules Checking the validity of passwords Configuring authentication errors and sessions Configuring Active Directory Connection • Published/reviewed: 2026-04-20 • Revision 022 • … Read More
Security Profile: Checking the device Note: If you have installed firmware 2025.0 and activated the Security Profile in the previous firmware version, you must perform a reset 1 after the update. Log in to the WBM. Return to topicHow do I get to the WBM again? Click… Read More