This site uses cookies for functional purposes. To continue please read and agree to our Data Privacy.

By closing this message, you consent to our use of cookies on this device.

PLCnext on Instagram  PLCnext on YouTube Github PLCnext CommunityStore PLCnext Community

  1. korhalepradip
  2. PLCnext Technology & PLCnext Controls
  3. Tuesday, 15 January 2019

I am trying to diagnostic axioline DI DO from PDI Read FB. I am able to diagnosis DI but not DO.(Not getting any value in Byte array)

DO card 2688349.

 

Martin PLCnext Team Accepted Answer Pending Moderation
0
Votes
Undo

Hello,

I would like to investigate this. Please post an example that demonstrates the problem. A simple example would be best.

Please also confirm the versions of PC Worx Engineer and PLCnext Firmware that you are using.

- Martin.

Phoenix Contact Electronics Headquarters - PLCnext Runtime Product Management and Support

korhalepradip Accepted Answer Pending Moderation
0
Votes
Undo

Sorry for the late response.

Please find the back up in below link.(Valid for 168Hrs only).

Address: https://extrans.phoenixcontact.com/extrans2/index.jsp?id=2024522799
Password: wwedCshjxN
korhalepradip Accepted Answer Pending Moderation
0
Votes
Undo

Hello Sir,

Waiting for your response.

Please find the back up in below link.

Address: https://extrans.phoenixcontact.com/extrans2/index.jsp?id=895283384
Password: lPMozm4w4A
Martin PLCnext Team Accepted Answer Pending Moderation
0
Votes
Undo

Hello Pradip,

Sorry for the delay, it has been extremely busy here.

I have now had a brief look at your project, and I notice that the array that receives the response from the I/O module is 20 bytes in length.

According to the documentation of the DO module (2688349), hardware revision 03 returns 116 bytes of data in response to request code 0x18. If this is the problem, then you should see STATUS[0] = 0x09B0 and STATUS[1] = 0x000B, indicating that the array is too small to receive the response.

Can you please confirm (a) the hardware revision of the Digital Output module that you are using, and (b) what (if any) error codes you are seeing in response to PDI request number 0x18.

I can also recommend upgrading your controller to Firmware version 2019.0 LTS, although I do not think this is part of the problem.

- Martin.

Phoenix Contact Electronics Headquarters - PLCnext Runtime Product Management and Support

  • Page :
  • 1


There are no replies made for this post yet.
However, you are not allowed to reply to this post.